Air Scrubber & Negative-Air CFM Sizing
Work out the airflow and number of HEPA air scrubbers a containment needs, from the room dimensions and your target air changes per hour (ACH) — an IICRC/AHAM sizing rule of thumb.
Calculator
A 2,700 cu ft room at 4 air changes per hour needs about 180 CFM (ACH × volume ÷ 60), so 1 scrubber at ~500 CFM each. Containment usually targets 4–6 ACH. These are labeled planning typicals — a certified technician confirms the setup.
During a mold, sewage or fire remediation, the work area is sealed off and put under negative pressure so contaminated air cannot drift into clean rooms. HEPA air scrubbers pull air through the containment and filter it, and the number you need depends on one thing: how many times per hour you want to exchange all the air in the room — the air changes per hour (ACH) target.
This is a sizing helper, not a cost tool. It turns the room dimensions and your ACH target into a required airflow in CFM and a scrubber count, using the same identity restoration technicians use in the field.
Formula
The math is two clean identities:
volume = length × width × heightrequired CFM = ACH × volume ÷ 60scrubbers = ceil(required CFM ÷ scrubber CFM)
- volume — the room in cubic feet.
- ACH — target air changes per hour (this is the inverse of the ACH = CFM × 60 ÷ volume identity used to verify a setup). Containment usually targets 4–6 ACH.
- ÷ 60 — converts changes-per-hour to airflow-per-minute (CFM).
- ceil() — you cannot deploy a fraction of a scrubber, so round up.
The ACH target and the per-unit CFM are labeled planning typicals you can override to match the machines on the truck.
Worked example
Take a room 15 ft × 20 ft × 9 ft and a target of 4 ACH for general clearance, with 500 CFM scrubbers:
volume = 15 × 20 × 9 = 2,700 cu ftrequired CFM = 4 × 2,700 ÷ 60 = 180 CFMscrubbers = ceil(180 ÷ 500) = 1 unit
Raise the goal to 6 ACH for active containment and the requirement rises to 270 CFM — still one 500-CFM scrubber, but with less headroom. A larger or taller room, or a higher ACH, is what tips you into a second unit.
Air changes, negative pressure and what a scrubber is not
Why 4–6 ACH? Restoration practice targets enough air movement to keep airborne particulate low and to hold the containment under negative pressure, without over-drying or creating so much turbulence that settled spores are re-suspended. Lower targets (around 4 ACH) suit general indoor-air clearance and post-remediation verification; higher targets (around 6 ACH, and sometimes more) suit active containment during aggressive removal. The right number is a professional judgment based on the contaminant, the materials and how the space is sealed — which is exactly why this is a labeled planning helper, not a specification.
Two practical notes. First, a HEPA scrubber’s rated CFM drops as its filters load, so techs size with a margin and monitor pressure with a manometer rather than trusting the nameplate number all day. Second, an air scrubber is not the same as a dehumidifier or an air mover: scrubbers clean and exchange air, air movers push evaporation off wet surfaces, and dehumidifiers pull moisture out of the air. A drying job needs the first two sized together — use the structural drying equipment tool for the air-mover and dehumidifier counts.
This helper deliberately stays inside the restoration lane: it sizes negative-air / scrubber CFM for containment and indoor-air-quality work, not HVAC ventilation, furnace CFM or a mechanical ventilation design (that is a different trade). To price the whole air-quality phase — duct cleaning, scrubber rental days and clearance testing — use the indoor air quality cost tool. Equipment counts here are IICRC/AHAM planning typicals; a certified technician must confirm the containment and airflow plan on site.
Reference table
The airflow you need scales with room volume and your target air changes per hour (ACH). These are labeled IICRC/AHAM planning typicals — a certified technician confirms the setup on site.
| Room volume | 4 ACH (IAQ / clearance) | 6 ACH (active containment) |
|---|---|---|
| 1,000 cu ft | 67 CFM | 100 CFM |
| 2,000 cu ft | 133 CFM | 200 CFM |
| 2,700 cu ft | 180 CFM | 270 CFM |
| 4,000 cu ft | 267 CFM | 400 CFM |
Identity: required CFM = ACH × volume ÷ 60; units = ceil(CFM ÷ scrubber CFM). See the air-changes / CFM table and sources.
Frequently asked questions
How many air scrubbers do I need?
What ACH should I target for containment?
How do I calculate room volume?
What is the difference between ACH and CFM?
ACH = CFM × 60 ÷ volume, which this tool rearranges to size the airflow you need.